General Description Size Height (With base): 5.5 cm (Ionization), 4.8cm (Heat), 5.0cm (Photoelectronic) Diameter: 10.2 cm Operating Temperature Range: 32°F to 100°F (0°C to 38°C) for heat, 32°F to 120°F (0°C to 49°C) for lonization, photoelectronic Operating Humidity Range: 5%-95% RH Latching Alarm: Reset by momentary power interruption Max Air Velocity: 4000ft/min (Photoelectronic), 2000ft/min (Ionization) Operating Voltage: 15 ~ 30VDC Standby Current: 50 µA Alarm Current: min 2mA @ 3.1VDC max 80mA @ 6.5VDC Maximum Ripple Voltage: 4 Volts peak to peak Sensitivity: 145°F (63°C) heat only The 800 series are 2-wire conventional low profile plug-in detectors designed to meet the performance criteria designated by UL. It is a low cost and high reliability series. A LED will be latched on to locally indicate alarm. The in (-) and out (-) terminals are short-circuited inside the detectors. When the detector is mounted , it will continue the wire to the next device or EOL resistor. When it is removed, the wire will be open for wiring supervision. 881 Model 881 is a 2-wire conventional ionization smoke detector that uses a state-of-the-art sensing chamber. These detectors are designed to provide open area protection and to be used with compatible UL listed panels only. 882 Model 882 is a 2-wire conventional photoelectronic smoke detector that use a state-of-the-art optical sensing chamber. This detector is designed to provide open area protection and to be used with compatible UL listed panels only. 885 Model 885 is a 2-wire conventional fixed temperature heat detector. These detectors are designed to provide open area protection and to be used with compatible UL listed panels only. The 800 series are UL listed. Models Available 885 This document is not intended to be used for installation purposes. 881 lonization Detector 882 Photoelectronic Detector 885 Heat DetectorSystem Sensor Worldwide Manufacturing & Distribution
|